214 P9 ASD Installation and Operation Manual
Trace Data 3
Program Utilities Trace
This parameter is used to select the Trace Data 3 item from Table 10 on pg.
252 to be read and stored in accordance with the setup of F740 and F741.
See F740 for additional information on this parameter.
Direct Access Number — F744
Parameter Type — Selection List
Factory Default — Output Current
Changeable During Run — Yes
Trace Data 4
Program Utilities Trace
This parameter is used to select the Trace Data 4 item from Table 10 on pg.
252 to be read and stored in accordance with the setup of F740 and F741.
See F740 for additional information on this parameter.
Direct Access Number — F745
Parameter Type — Selection List
Factory Default — DC Voltage
Changeable During Run — Yes
Baud Rate (RS485 2-Wire)
Program Communications Communication Settings
This parameter plays a role in the setup of the communications network by
establishing the Baud Rate of the communications link.
The communications network includes other ASDs and Host/Control computers
that monitor the status of the ASD(s), transfers commands, and loads or
modifies the parameter settings of the ASD.
Changes made to this parameter require that the power be cycled (off then on)
for the changes to take effect.
Settings:
0 — 9600
1 — 19200
2 — 38400
Direct Access Number — F800
Parameter Type — Selection List
Factory Default — 19200
Changeable During Run — Yes
Units — bps
Parity (RS485 2- and 4-Wire)
Program Communications Communication Settings
This parameter plays a role in the setup of the communications network by
establishing the Parity setting of the communications link.
The communications network includes other ASDs and Host/Control computers
that monitor the status of the ASD(s), transfers commands, and loads or
modifies the parameter settings of the ASD.
Changes made to this parameter require that the power be cycled (off then on)
for the changes to take effect.
Settings:
0 — No Parity
1 — Even Parity
2 — Odd Parity
Direct Access Number — F801
Parameter Type — Selection List
Factory Default — Even Parity
Changeable During Run — Yes
ASD Number
Program Communications Communication Settings
This parameter plays a role in the setup of the communications network by
assigning an identification (ID) number to each ASD in the communications
network.
The communications network includes other ASDs and Host/Control computers
that monitor the status of the ASD(s), transfers commands, and loads or
modifies the parameter settings of the ASD.
Changes made to this parameter require that the power be cycled (off then on)
for the changes to take effect.
Direct Access Number — F802
Parameter Type — Numerical
Factory Default — 0
Changeable During Run — Yes
Minimum — 0
Maximum — 247
F744 F802