218 P9 ASD Installation and Operation Manual
Point 2 Frequency
Program Communications Communication Reference Adjust
This parameter is used to set the gain and bias of the Communications
Reference speed control input.
See F811 for additional information on this parameter.
This parameter sets the Communications Reference Speed Setpoint 2.
Changes made to this parameter require that the power be cycled (off then on)
for the changes to take effect.
Direct Access Number — F814
Parameter Type — Numerical
Factory Default 60.00
Changeable During Run — Yes
Minimum — 0.00
Maximum — Maximum Freq. (F011)
Units — Hz
Baud Rate (RS485)
Program Communications Communication Settings
This parameter sets the RS485 baud rate.
Changes made to this parameter require that the power be cycled (off then on)
for the changes to take effect.
Settings:
0 — 9600 bps
1 — 19200 bps
2 — 38400 bps
Direct Access Number — F820
Parameter Type — Selection List
Factory Default 19200
Changeable During Run — Yes
RS485 Send Delay (4-Wire RS485)
Program Communications Communication Settings
This parameter sets the RS485 response delay time.
Changes made to this parameter require that the power be cycled (off then on)
for the changes to take effect.
Direct Access Number — F825
Parameter Type — Numerical
Factory Default 0.00
Changeable During Run — Yes
Minimum — 0.00
Maximum — 2.00
Units — Seconds
F814 F825