P9 ASD Installation and Operation Manual 87
Low-Speed Signal Output Frequency
Program Ter mi nal Reach Settings
The Low-Speed Signal Output Frequency parameter sets an ASD output
frequency threshold that activates the assigned discrete output terminal for the
duration that the ASD output speed is equal to or less than this setting.
Direct Access Number — F100
Parameter Type — Numerical
Factory Default 0.00
Changeable During Run — Yes
Minimum — 0.00
Maximum — Upper-Limit Freq. (F012)
Units — Hz
Speed Reach Frequency
Program Ter mi nal Reach Settings
The Speed Reach Frequency sets a frequency threshold that, when reached or
is within the bandwidth specified by parameter
F102, activates the assigned
discrete output terminal for the duration that the ASD output is within the F102
bandwidth.
Direct Access Number — F101
Parameter Type — Numerical
Factory Default 0.00
Changeable During Run — Yes
Minimum — 0.00
Maximum — Upper-Limit Freq. (F012)
Units — Hz
Speed Reach Detection Band
Program Terminal Reach Settings
This parameter sets the bandwidth of the Speed Reach Frequency (F101)
setting.
Direct Access Number — F102
Parameter Type — Numerical
Factory Default 2.50
Changeable During Run — Yes
Minimum — 0.00
Maximum — Upper-Limit Freq. (F012)
Units — Hz
Forward/Reverse Run Priority Selection
Program Ter mi nal Input Special Functions
The Forward/Reverse Priority Selection determines the operation of the ASD
if the F and R control terminals are activated simultaneously.
Settings:
0 — Reverse
1 — Suspend
The waveforms shown depict the motor response for all combinations of the F
and R terminal settings if the Reverse option is chosen.
The Suspend setting will decelerate the motor to a stop regardless of the
rotation direction when both the F and R control terminals are activated.
Direct Access Number — F105
Parameter Type — Selection List
Factory Default Suspend
Changeable During Run — No
Simultaneous F and R activation.
F100 F105

Table of Contents