3.2 Setting the Slave Device Configuration Information
Unified Controller nv series PROFIBUS(PA912) Module Instruction Manual
45
9
Download the registration details to the PA912.
Download the registration details to the PA912. Before downloading, connect
the computer to the PA912 CONFIG connector via a cable bundled to the
Anybus NetTool-PB.
Figure 3-17 Downloading to the PA912
Note
・
If Transport Paths of the Anybus NetTool-PB has not been set, the Transport Paths window
will open. Make settings for the serial port in the [Serial] tub.
For details, refer to the Anybus NetTool-PB Instruction Manual.
Important
•
When downloading the registration details to the PA912, nv controller should be in HALT
condition and PA912 should be in initial condition (the condition that the DC24V power supply
to the PA912 module has turned off, and “COM”, “MODE” and “TOK” of the PROFIBUS status
display LED are OFF status). Otherwise an error may occur during the download of the
registration details.
•
After downloading the registration details to the PA912, turn off the DC24V power supply to the
PA912 module once, and turn it on again. Otherwise the settings downloaded will not be
enabled.