6F3B0250
160
T1/T1S User’s Manual
7. Instructions
FUN 026 TNOT Table invert transfer
Expression
Input
-
[
A
TNOT (
n
)
B
]
-
Output
Function
When the input is ON, the data of
n
registers starting with
A
are bit-inverted and transferred to
n
registers starting with
B
in a block. The allowable range of the table size
n
is 1 to 1024 words.
Execution condition
Input Operation Output
OFF No execution OFF
ON Execution ON
Operand
Name Device Re
g
ister Constant Index
X Y R S T. C. XW YW RW SW T C D I J K
A
Start of source
ÖÖÖÖÖÖÖ
n
Table size 1 - 1024
B
Start of
destination
ÖÖÖÖÖÖ
Example
When R010 is ON, the data of D0600 to D0604 (5 registers) are bit-inverted and transferred to
D0865 to D0869, and the output is turned ON.
D0600 H00FF D0865 HFF00
D0601 H0000 Bit-invert D0866 HFFFF
D0602 H1234 and transfer D0867 HEDCB 5 registers
D0603 H5555 D0868 HAAAA
D0604 H89AB D0869 H7654
Note
·
The source and destination tables can be overlapped.
T1S only