Q9 ASD Installation and Operation Manual 161
Communications Option (DeviceNet/Profibus) Setting 10
No Path — Direct Access Only
—FUNCTION NOT AVAILABLE WITH THE Q9 ASD—
Same as F841. See F841 for information on this parameter.
Direct Access Number — F843
Parameter Type — Selection List
Factory Default0
Changeable During Run — Yes
Communications Option (DeviceNet/Profibus) Setting 11
No Path — Direct Access Only
—FUNCTION NOT AVAILABLE WITH THE Q9 ASD—
Same as F841. See F841 for information on this parameter.
Direct Access Number — F844
Parameter Type — Selection List
Factory Default0
Changeable During Run — Yes
Communications Option (DeviceNet/Profibus) Setting 12
No Path — Direct Access Only
—FUNCTION NOT AVAILABLE WITH THE Q9 ASD—
Same as F841. See F841 for information on this parameter.
Direct Access Number — F845
Parameter Type — Selection List
Factory Default0
Changeable During Run — Yes
Communications Option (DeviceNet/Profibus) Setting 13
No Path — Direct Access Only
—FUNCTION NOT AVAILABLE WITH THE Q9 ASD—
Same as F841. See F841 for information on this parameter.
Direct Access Number — F846
Parameter Type — Selection List
Factory Default0
Changeable During Run — Yes
Disconnection Detection Extended Time
No Path — Direct Access Only
This parameter is used to set the length of time that no communications activity
may exist before the communications link is disconnected.
Direct Access Number — F850
Parameter Type — Numerical
Factory Default — 0.0
Changeable During Run — Yes
Minimum — 0.0
Maximum — 100.0
Units — Seconds
ASD Operation at Disconnect
No Path — Direct Access Only
This parameter is used to set the Q9 ASD action to be carried out in the event of
the loss of communications.
Settings:
0 — Stop and Release (End) Communication
1 — Do Nothing (Continue Programmed Operation)
2 — Deceleration Stop
3 — Coast Stop
4 — Emergency Off
5 — Preset Speed (Setting of F852)
Direct Access Number — F851
Parameter Type — Selection List
Factory DefaultStop, Release
Communication
Changeable During Run — Yes
F843 F851