166 Q9 ASD Installation and Operation Manual
Ext. Comm. Cfg. 2
No Path — Direct Access Only
This parameter sets the Modbus RTU network characteristics: Baud Rate, Parity,
and Stop Bits. See the table below for the parameter settings.
Direct Access Number — F883
Parameter Type — Numerical
Factory Default — 0
Changeable During Run — Yes
Minimum — 0
Maximum — 255 (only 0 – 19 effective)
Ext. Comm. Cfg. 3
No Path — Direct Access Only
This parameter Enables/Disables the network time-out timer. The timer is enabled
by setting this parameter to a non-zero value (1 – 255). The timer is disabled by
setting this value to zero.
Once started, the complete packet must be received before the timer expires or an
error will be incurred.
Direct Access Number — F884
Parameter Type — Numerical
Factory Default — 0
Changeable During Run — Yes
Minimum — 0
Maximum — 255
Units — Seconds
Setting Baud Rate Parity Stop Bits
0
2400
Odd
1
1Even
2 None
3
4800
Odd
4Even
5 None
6
9600
Odd
7Even
8 None
9
19200
Odd
10 Even
11 None
12
38400
Odd
13 Even
14
None
15 2400
2
16 4800
17 9600
18 19200
19 38400
Note: An improper parameter setting will result
in a Communication error.
F883 F884