Q9 ASD Installation and Operation Manual 183
Virtual Input Terminal 1 Selection
No Path — Direct Access Only
This parameter is used to set the functionality of the Virtual Input Terminal 1.
As a virtual terminal, it exists only in memory and is considered to always be in
its True (or connected to CC) state.
It is often practical to assign a function to this terminal that the user desires to be
maintained regardless of external conditions or operations.
This parameter sets the programmable Virtual Input Terminal 1 terminal to 1 of
the functions that are listed in Table 4 on pg. 186.
In addition, the input terminal must be specified as Normally Open or Normally
Closed.
Direct Access Number — F973
Parameter Type — Selection List
Factory DefaultUnassigned
Changeable During Run — No
Virtual Input Terminal 2 Selection
No Path — Direct Access Only
This parameter is used to set the functionality of the Virtual Input Terminal 2.
As a virtual terminal, it exists only in memory and is considered to always be in
its True (or connected to CC) state.
It is often practical to assign a function to this terminal that the user desires to be
maintained regardless of external conditions or operations.
This parameter sets the programmable Virtual Input Terminal 2 terminal to 1 of
the functions that are listed in Table 4 on pg. 186.
In addition, the input terminal must be specified as Normally Open or Normally
Closed.
Direct Access Number — F974
Parameter Type — Selection List
Factory DefaultUnassigned
Changeable During Run — No
Virtual Input Terminal 3 Selection
No Path — Direct Access Only
This parameter is used to set the functionality of the Virtual Input Terminal 3.
As a virtual terminal, it exists only in memory and is considered to always be in
its True (or connected to CC) state.
It is often practical to assign a function to this terminal that the user desires to be
maintained regardless of external conditions or operations.
This parameter sets the programmable Virtual Input Terminal 3 terminal to 1 of
the functions that are listed in Table 4 on pg. 186.
In addition, the input terminal must be specified as Normally Open or Normally
Closed.
Direct Access Number — F975
Parameter Type — Selection List
Factory DefaultUnassigned
Changeable During Run — No
Virtual Input Terminal 4 Selection
No Path — Direct Access Only
This parameter is used to set the functionality of the Virtual Input Terminal 4.
As a virtual terminal, it exists only in memory and is considered to always be in
its True (or connected to CC) state.
It is often practical to assign a function to this terminal that the user desires to be
maintained regardless of external conditions or operations.
This parameter sets the programmable Virtual Input Terminal 4 terminal to 1 of
the functions that are listed in Table 4 on pg. 186.
In addition, the input terminal must be specified as Normally Open or Normally
Closed.
Direct Access Number — F976
Parameter Type — Selection List
Factory DefaultUnassigned
Changeable During Run — No
F973 F976