198 Q9 ASD Installation and Operation Manual
*DC Over-Volts DC Bus Voltage Exceeds Specifications.
ASD is attempting to start into a spinning motor
after a momentary power loss.
Incoming commercial power voltage level is
above the specified range.
Deceleration time is too short.
Voltage spikes at the 3-phase input; install
inductive filter.
Over-Voltage Stall feature is turned off.
System is regenerating.
Load fluctuations.
*DC Under-Volts
Under-Voltage Condition at the 5, 15, or
the 24 VDC supply.
Defective control board.
Excessive load on power supply.
Low input voltage.
Emergency Off Emergency Off.
Stop-Reset pressed twice at the EOI.
E-OFF command received remotely.
Heavy Load Motor/ASD Over Loaded.
Acceleration time is too short.
ASD is improperly matched to the application.
Excessive load.
Light Load Light Load. ASD is improperly matched to the application.
Lower Limit Lower-Limit Time. Parameter F256 adjustment required.
Main Under-Volts
Under-Voltage (Main Circuit Power
Supply).
3-phase input voltage low.
Defective control board.
Excessive load on power supply.
Under-Voltage/Ridethrough settings require
adjustment.
Motor Overload Motor Overload.
V/f setting require adjustment.
Motor is locked.
Continuous operation at low speed.
Motor is improperly matched to the load.
Note: * Reset ignored if active.
Table 11. Alarms (Continued)
EOI Display Fault Description Possible Cause