Q9 ASD Installation and Operation Manual 71
Always ON 1 Terminal 1
No Path — Direct Access Only
This parameter is used to set the functionality of the virtual discrete input terminal
ON. As a virtual terminal, the ON control terminal exists only in memory and is
considered to always be in its True (or connected to CC) state.
It is often practical to assign a function to this terminal that the user desires to be
maintained regardless of external conditions or operations.
This parameter sets the programmable ON terminal to any of the user-selectable
functions listed in Table 4 on pg. 186.
Direct Access Number F110
Parameter Type — Selection List
Factory DefaultUnassigned
Changeable During Run — No
F Terminal
Program Input Terminals
This parameter is used to set the functionality of the F discrete input terminal.
In addition, this input terminal must be specified as Normally Open or Normally
Closed.
This parameter sets the programmable F terminal to any of the user-selectable
functions listed in Table 4 on pg. 186.
Direct Access Number F111
Parameter Type — Selection List
Factory DefaultForward Forward
Changeable During Run — No
R Terminal
Program Input Terminals
This parameter is used to set the functionality of the R discrete input terminal.
In addition, this input terminal must be specified as Normally Open or Normally
Closed.
This parameter sets the programmable R terminal to any of the user-selectable
functions listed in Table 4 on pg. 186.
Direct Access Number F112
Parameter Type — Selection List
Factory DefaultReverse Reverse
Changeable During Run — No
ST Terminal
Program Input Terminals
This parameter is used to set the functionality of the ST discrete input terminal.
In addition, this input terminal must be specified as Normally Open or Normally
Closed.
This parameter sets the programmable ST terminal to any of the user-selectable
functions listed in Table 4 on pg. 186.
Direct Access Number F113
Parameter Type — Selection List
Factory DefaultStandby Standby
Changeable During Run — No
RES Terminal
Program Input Terminals
This parameter is used to set the functionality of the RES discrete input terminal.
In addition, this input terminal must be specified as Normally Open or Normally
Closed.
This parameter sets the programmable RES terminal to any of the user-selectable
functions listed in Table 4 on pg. 186.
Direct Access Number F114
Parameter Type — Selection List
Factory DefaultReset Reset
Changeable During Run — No
F110 F114