128 https://www.toshiba.com/tic/
Direct Access Parameter Information
Q9 Plus ASD Install/Op Manual
Jog Stop Pattern
Program Frequency Jog Settings
This parameter sets the stopping method used while operating in
the Jog mode.
Note: This parameter setting is used for the Jog operation only.
The Emergency Off stopping method setting of parameter
F603
has priority over this setting and changes made here
do not affect the function or setting of parameter
F603
.
Settings:
0 — Deceleration
1 — Coast
2 — DC Injection
Direct Access Number —
F261
Parameter Type — Selection List
Factory Default — Deceleration
Changeable During Run — No
EOI Keypad Operation Jog Mode
Program Frequency Jog Settings
This parameter enables the Jog command to be received from
the EOI. When disabled, the Jog command received from the
EOI is ignored.
Jog commands may also be received from the Terminal Board.
Priority as to which is allowed to override the other is selected at
F106.
The priority selection at F106 enables the selected source for Jog
control and disables the other. The F106 setting overrides the
F262 parameter setting.
Settings:
0 — Disabled
1 — Enabled
Direct Access Number —
F262
Parameter Type — Selection List
Factory Default — Disabled
Changeable During Run — Yes
F261 – F264