Direct Access Parameter Information
Q9 Plus ASD Install/Op Manual
https://www.toshiba.com/tic/ 145
Commercial Power/ASD Switching Frequency
Program Terminal Line Power Switching
When enabled at F354 and with a properly configured discrete
output terminal, this parameter sets the frequency at which the At
Frequency Powerline Switching function engages.
The At Frequency Powerline Switching function commands the
system to discontinue using the output of the ASD and to switch
to commercial power once reaching the frequency set here.
See F354 for additional information on this parameter.
Direct Access Number —
F355
Parameter Type — Numerical
Factory Default — (ASD-Depen-
dent)
Changeable During Run — Yes
Minimum — 0.00
Maximum — Upper-Limit Freq.
(F012)
Units — Hz
ASD Side-Switching Delay Time
Program Terminal Line Power Switching
This parameter determines the amount of time that the ASD will
wait before outputting a signal to the motor once the switch-to-
ASD-output criteria has been met.
See F354 for additional information on this parameter.
Direct Access Number —
F356
Parameter Type — Numerical
Factory Default — (ASD-Depen-
dent)
Changeable During Run — Yes
Minimum — 0.10
Maximum — 10.00
Units — Seconds
Commercial Power Side Switching Delay Time
Program Terminal Line Power Switching
This parameter determines the amount of time that the ASD will
wait before allowing commercial power to be applied to the motor
once the switch-to-commercial-power criteria has been met.
See F354 for additional information on this parameter.
Direct Access Number —
F357
Parameter Type — Numerical
Factory Default — 0.62
Changeable During Run — Yes
Minimum — 0.40
Maximum — 10.00
Units — Seconds
Commercial Power Switching Freq. Hold Time
Program Terminal Line Power Switching
This parameter determines the amount of time that the connec-
tion to commercial power is maintained once the switch-to-ASD-
output criteria has been met.
See F354 for additional information on this parameter.
Direct Access Number —
F358
Parameter Type — Numerical
Factory Default — 2.00
Changeable During Run — Yes
Minimum — 0.10
Maximum — 10.00
Units — Seconds
F355 – F359