Direct Access Parameter Information
Q9 Plus ASD Install/Op Manual
https://www.toshiba.com/tic/ 149
Process Increasing Rate
Program Feedback Feedback Settings
This parameter is used to limit the rate that the output of the ASD
may increase for a given difference in the speed reference and
the PID feedback value.
Direct Access Number
F372
Parameter Type — Numerical
Factory Default — 10.0
Changeable During Run — Yes
Minimum — 0.1
Maximum — 600.0
Units — Seconds
Process Decreasing Rate
Program Feedback Feedback Settings
This parameter is used to limit the rate that the output of the ASD
may decrease for a given difference in the speed reference and
the PID feedback value.
Direct Access Number
F373
Parameter Type — Numerical
Factory Default — 10.0
Changeable During Run — Yes
Minimum — 0.1
Maximum — 600.0
Units — Seconds
Frequency Command Detection Range
Program Feedback Feedback Settings
While operating in the PID mode, this parameter reads the feed-
back frequency. Once the feedback frequency is within the set-
ting of this parameter (F374) relative to the commanded
frequency, a properly configured output terminal is activated.
Available output terminal settings for this parameter include: FC =
RR, FC = RX, and FC = VI (see Table 12 on page 257), where
FC is the frequency command and RR, RX, and VI are the input
terminals of the received feedback.
Direct Access Number
F374
Parameter Type — Numerical
Factory Default — (ASD-Depen-
dent)
Changeable During Run — Yes
Minimum — 0.00
Maximum Maximum Freq.
(F011)
Units — Hz
Number of PG Input Pulses
Program Feedback PG Settings
This parameter is used to set the number of pulses output from a
shaft-mounted encoder that is used to indicate one revolution of
rotation (360°) of the motor or of the motor-driven equipment.
Direct Access Number
F375
Parameter Type — Numerical
Factory Default — 500
Changeable During Run — No
Minimum — 1
Maximum — 9999
Number of PG Input Phases
Program Feedback PG Settings
This parameter determines the type of information that is sup-
plied by the phase encoder.
Settings:
1 — Single Phase
2 — Two Phase
3 — Two Phase (Polarity Inversion)
Direct Access Number
F376
Parameter Type — Selection List
Factory Default — Two Phase
Changeable During Run — No
F372F377