Direct Access Parameter Information
Q9 Plus ASD Install/Op Manual
AM Output Terminal Function
Program Terminal Analog Output Terminals
This setting determines the output function of the AM analog out-
put terminal. The AM output terminal produces an output voltage
or current that is proportional to the magnitude of the function
assigned to this terminal. Configure the DVM, as shown below, in
accordance with the output signal type of interest (i.e., current or
voltage).
The available assignments for this output terminal are listed in
Table 10 on page 255.
Note: If the monitored item has a positive and a negative
component, use the Expansion I/O Card 2 (P/N ETB004Z).
See the Expansion IO Card Option 2 instruction manual
(P/N 58686) for additional information on the functions of
the option card.
See F678 for additional information on this parameter.
To read Voltage at this terminal, configure the meter to read DC
voltage, and connect the leads of the meter to AM (+) and
CCA (-).
To read Current at this terminal, configure the meter to read DC
current, and connect the leads of the meter to AM (+) and
CCA (-).
AM Terminal Setup Parameters
F670 — Set AM Function
F671 — Calibrate AM Terminal
F685 — Output Response Polarity Selection
F686 — Set Zero Level
Direct Access Number —
F670
Parameter Type — Selection List
Factory Default — Output Cur-
rent
Changeable During Run — Yes
AMAM
F670 – F671