EasyManua.ls Logo

Toshiba Q9+ - Page 244

Toshiba Q9+
306 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
232 https://www.toshiba.com/tic/
Direct Access Parameter Information
Q9 Plus ASD Install/Op Manual
Input Function Target 3
Program My Function My Function Unit 3
This parameter plays a role in the setup of the My Function fea-
ture by selecting the functionality of the programmable Input
Function Target 3 terminal.
This setting assigns the function of the programmable Input
Function Target 3 terminal to any one of the user-selectable func-
tions listed in Table 11 on pg. 256, Table 12 on pg. 257, or Table
14 on pg. 260.
See F977 for additional information on this parameter.
Direct Access Number
F916
Parameter Type — Selection List
Factory Default — 0 (Disabled)
Changeable During Run — No
Output Function Assigned
Program My Function My Function Unit 3
This parameter plays a role in the setup of the My Function fea-
ture by selecting the functionality of the Output Function
Assigned terminal.
This setting assigns the function of the programmable Output
Function Assigned data location to one of the functions listed in
the Input Setting field of Table 12 on pg. 257.
Settings:
0 – 3099
See the My Function Instruction Manual (P/N E6581335) and
F977 for additional information on this parameter.
Direct Access Number
F917
Parameter Type — Selection List
Factory Default — 0 (Disabled)
Changeable During Run — No
My Function Percent Data 1
Program My Function My Function Data
This parameter is used to set the trigger threshold level of the
analog signal of the My Function Percent Data 1.
The analog signal is selected using the Input Setting number
from Table 12 on page 257.
Once the assigned output value reaches the threshold setting of
this parameter the output value is transferred to My Function Out
1.
See the My Function Instruction Manual (P/N E6581335) and
F977 for additional information on this parameter.
Direct Access Number
F918
Parameter Type — Numerical
Factory Default — 0.00
Changeable During Run — Yes
Minimum — 0.00
Maximum — 200.00
Units — %
My Function Percent Data 2
Program My Function My Function Data
This parameter is used to set the trigger threshold level of the
analog signal of the My Function Percent Data 2.
The analog signal is selected using the Input Setting number
from Table 12 on page 257.
Direct Access Number
F919
Parameter Type — Numerical
Factory Default — 0.00
Changeable During Run — Yes
Minimum — 0.00
Maximum — 200.00
Units — %
F916F920

Table of Contents

Related product manuals