Cable/Terminal Specifications
Q9 Plus ASD Install/Op Manual
282 https://www.toshiba.com/tic/
Cable/Terminal
Specifications
Installation should conform to NEC Article 110
(Requirements for Electrical Installations), all
regulations of the Occupational Safety and Health
Administration, and any other applicable national,
regional, or industry codes and standards.
The following ratings are guidelines and shall not
be the sole determining factor of the lug or wire size
used with the Q9 Plus ASD. Application-specific
applicables, wire insulation type, conductor
material, and local and regional regulations are but
a few of the considerations when selecting the
actual lug and wire type to be used with the Q9 Plus
ASD.
Note: Cable/Terminal specifications are
based on the rated current of the Q9
Plus ASD and Do Not include the 10%
Service Factor.
Note: Use only 75° C copper wire/cable for
motor and power connections.
Table 24. 230-Volt Q9 Plus ASD Cable/Terminal/Torque Specifications.
Model
Number
VT130Q9+
Wire/Cable Size Lug Size Range
Terminal
Board Wire
Size
Torque
AWG or kcmil
Input/Output Power
Wire-Size/Lug-
Capacity for
Input/Output Power
In-Lbs./N·m
Recommended Maximum 3Ø-Input 3Ø-Output
TB1 – 4
Terminals
3Ø-Input -Output
2015 14 10
14 to 10
20
(3-core shield)
Torque to 5.3/
0.6
12.4/1.4
2025 14 10
2035 14 10
2055 10 10
2080 8 8 12 to 8
26.6/3
2110 8 8 10 to 4
2160 6 3
8 to 2 47.8/5.4
2220 4 3
2270 3 3
4 to 1/0 212/24
2330 2 2
2400 1/0 4/0 2 to 300 360/41
2500 1/0 4/0
6 to 250 2 to 300 275/31 168/19
2600 3/0 4/0
2750 *3/0 *4/0
6 to 250 275/31
210K *3/0 *4/0
212K *3/0 *4/0
2750RD *3/0 *4/0
210KRD *3/0 *4/0
212KRD *3/0 *4/0
Note: (*) Indicates that the item is one of a set of two (listed type) parallel cables.
RD Suffix = DCL Included.