BACnet Setup
Q9 Plus ASD Install/Op Manual
https://www.toshiba.com/tic/ 69
Binary Value
#7 (BV7)
Drive Ready
Indicates if the drive is ready to run
(ST and Run Command)
Ready/
Not Ready
R
Binary Value
#8 (BV8)
At Set-Point
Indicates if the drive has reached its
target speed
Reached/
No
R
Binary Value
#10 (BV10)
Run/Stop
Cmd
Commands the drive to start Start/Stop C
Binary Value
#11 (BV11)
Fwd/Rev Cmd
Commands the rotation direction of the
drive
Rev/Fwd C
Binary Value
#14 (BV14)
Fault Reset Commands the drive to reset a fault Reset/No C
Binary Value
#18 (BV18)
Preset Spd 1 Commands the Preset Speed 1 operation SP1/None C
Binary Value
#19 (BV19)
Preset Spd 2 Commands the Preset Speed 2 operation SP2/None C
Binary Value
#20 (BV20)
Preset Spd 3 Commands the Preset Speed 3 operation SP3/None C
Binary Value
#21 (BV21)
Freq Ovrd
Overrides the Frequency Mode 1 (F004)
selection
Enabled/
Off
C
Binary Value
#22 (BV22)
Cmd Ovrd
Overrides the Command Mode (F003)
selection
Enabled/
Off
C
R = Read-only; C = Commandable
Table 6. BACnet
®
Analog Inputs.
Analog Input
Terminal
Analog Input
Object ID
Object Name Description Value Access
RR
Analog
Input #0
(AI0)
RR Level
Input level of the RR
analog input
Percent
(%) of full
scale
R
V/I
Analog
Input #1
(AI1)
V/I Level
Input level of the V/I
analog input
Percent
(%) of full
scale
R
RX
Analog
Input #2
(AI2)
RX Level
Input level of the RX
analog input
Percent
(%) of full
scale
R
AI1*
Analog
Input #3
(AI3)
AI1 Level
Input level of the AI1
analog input
Percent
(%) of full
scale
R
AI2*
Analog
Input #4
(AI4)
AI2 Level
Input level of the AI2
analog input
Percent
(%) of full
scale
R
* The ETB004Z expansion I/O card is required to use this input.
R = Read-only
Table 5. BACnet
®
Binary Values.(Cont)
Binary Value
Object ID