BACnet Setup
Q9 Plus ASD Install/Op Manual
https://www.toshiba.com/tic/ 71
Table 8. BACnet
®
Analog Values.
Analog Value
Object ID
Object Name Description Value Access
Analog
Value #0
(AV0)
Output Speed
Output speed (output frequency / base
frequency
x motor nameplate rpm, ie. 30 / 60 x
1770 = 885)
RPM R
Analog
Value #1
(AV1)
Output Freq Frequency output Hz R
Analog
Value #2
(AV2)
DC Bus Volt DC bus voltage V R
Analog
Value #3
(AV3)
Output Volt Voltage output to the motor V R
Analog
Value #4
(AV4)
Output Current Current generated by the motor A R
Analog
Value #5
(AV5)
Output Torque Torque generated by the motor % R
Analog
Value #6
(AV6)
Input Power Power consumed by the drive kW R
Analog
Value #7
(AV7)
Output Power Power consumed by the motor kW R
Analog
Value #8
(AV8)
Total Input
Power
Total cumulative power consumed by
the drive
kWh R
Analog
Value #9
(AV9)
Total Output
Power
Total cumulative power consumed by
the motor
kWh R
Analog
Value #10
(AV10)
PID Fbck PID feedback value Hz R
Analog
Value #11
(AV11)
Run Time Total time of operation Hours R

Table of Contents