BACnet Setup
Q9 Plus ASD Install/Op Manual
72 https://www.toshiba.com/tic/
Analog
Value #12
(AV12)
VLP
Technology
Average
Average operating Virtual Linear Pump
number
- R
Analog
Value #13
(AV13)
VLP
Technology
Feedback
Virtual Linear Pump process feedback - R
Analog
Value #14
(AV14)
VLP
Technology
Direct Ref
Virtual Linear Pump direct mode com-
mand reference
- C
Analog
Value #15
(AV15)
VLP
Technology
Process Hold
Ref
Virtual Linear Pump process hold
mode command
reference
- C
Analog
Value #16
(AV16)
Freq Ref Frequency reference Hz C
Analog
Value #18*
(AV18)
Last Flt Current fault code - R
Analog
Value #19*
(AV19)
Prev Flt 1 Most recent fault code - R
Analog
Value #20*
(AV20)
Prev Flt 2 Second most recent fault code - R
Analog
Value #23
(AV23)
Accel Time 1 Changes Acceleration Time 1 (F009) Sec W
Analog
Value #24
(AV24)
Decel Time 1 Changes Deceleration Time 1 (F010) Sec W
* Refer to the
BACnet
®
Option Unit Function Manual
for the list of fault codes.
R = Read-only; C = Commandable; W = Writable
Table 8. BACnet
®
Analog Values.(Cont)
Analog Value
Object ID
Object Name Description Value Access