FILE NO. SVM-13069-3
10-4-5. Indoor Unit Fixing
1. Pass the pipe through the hole in the wall and
hook the indoor unit on the upper hook of the
installation plate.
2. Swing the indoor unit to right and left to confirm
that it is firmly hooked up on the mounting plate.
3. While pressing the indoor unit onto the wall,
hook in at the lower section of the mounting plate.
Pull the indoor unit toward you to confirm that it is
firmly hooked up on the mounting plate.
CAUTION
Fig. 10-4-22
• To detach the indoor unit from the mounting plate,
pull the indoor unit toward you while pushing its
bottom up as shown in the figure.
Fig. 10-3-23
PushPush
Press (unhook)
1
Installation
plate
Hook here
2
Hook
1
10-4-6. Drainage
1. Run the drain hose slopping downward.
NOTE :
• The hole should be made at a slight downward
slant on the outdoor side.
Fig. 10-4-24
2. Put water in the drain pan and make sure that the
water is drained out.
3.
When connecting an extension drain hose,
insulate it with shield pipe.
Fig. 10-4-25
Shield pipe
Extension drain hose
Inside the room
Drain hose
Space for
pipes
Wall
Drain
guide
Fig. 10-4-26
– 65 –
CAUTION
Arrange the drain pipe for proper drainage from
the unit.
Improper drainage can result in dew-dropping.
This air conditioner has the structure designed
to drain water collected from dew, which forms
on the back of the indoor unit, to the drain pan.
Therefore, do not store the power cord and other
parts at a height above the drain guide.
• The drain is internally trapped
An external trap is not required