7-2. Operation Data
<Cooling>
<Heating>
NOTES :
1. Measure surface temperature of heat exchanger pipe around center of heat exchanger path U bent.
(Thermistor themometer)
2. Connecting piping condition : 5 m
Model name Standard Indoor Outdoor Compressor
RAS- pressure fan mode fan mode revolution
Indoor Outdoor P (MPa) T1 (°C) T2 (°C) (rps)
27/19 35/-
10BKV-E1
0.8 to 1.0
11 to 12
52 to 53
High High
58
13BKV-E1
0.7 to 0.9 11 to 12 49 to 50
High High
80
condition(°C)
Tempeature Heat exchanger
pipe temp.
Model name Standard Indoor Outdoor Compressor
RAS- pressure fan mode fan mode revolution
Indoor Outdoor P (MPa) T1 (°C) T2 (°C) (rps)
20/- 7/6
2.5 to 2.7 42 to 43
0 to 1 High High
68
2.6 to 2.7 43 to 44
0 to 1 High High
73
condition(°C)
Tempeature Heat exchanger
pipe temp.
10BKV-E1
13BKV-E1
FILE NO. SVM-17030
- 20 -