30
Item
2. Indoor fan
motor control
Operation flow and applicable data, etc.
<In heating operation>
Description
1) When setting the fan speed to L,
L+, M, M+, H or Quiet on the remote
controller
, the operation is per-
formed with the constant speed
shown in Fig. 3 and Table 1.
2) When setting the fan speed to
AUTO on the remote controller,
revolution of the fan motor is
controlled to the fan speed level
shown in Fig. 5 according to the set
temperature and room temperature.
3) Min air flow rate is controlled by
temperature of the indoor heat
exchanger (Tc) as shown in Fig. 4.
4) Cold draft prevention, the fan
speed is controlled by temperature
of the indoor heat exchanger (Tc)
as shown in Fig. 6.
In starting In stability
Until 12 minutes
passed aft
er
ope
ra
tion
st
a
r
t
When
12 to 25 minutes passed after operation
start and room temperature is 3°C or lower than
set temperature.
When 12 to 25 minutes passed after operation start
and room temperature is higher than (set temperature
–3°C)
FAN AUTO
When 25 minutes or more passed after operation start
FAN Manual
Room temperature < Set temperature –4°C
Room temperature Set temperature –3.5°C
(Fig. 3)
(Fig. 4)
Cold draft preventive control
(Fig. 6)
Fan spee
d
A
U
T
O
Basi
c
fan
co
ntr
ol
* No limitation while fan speed MANUAL mode is in stabilit
y.
* A: Wh
e
n T
sc
24
,
A is 24
,
and when Tsc < 24
,
A is Ts
c
Tsc: Set valu
e
TS
C
T
A
[
°
C
]
b
0
.
5
c
–1.0
d
–1.5
e
–2.0
f
–2.5
g
–5.0
5
.
5
L+ (W9)
*1
*2
*3
H
(
WE
)
H
(
WE
)
Line-approximate
H and S
U
L with Tc
.
SUL
(
W2
)
Stop
45
Tc
33
44 32
33 21
32 20
*A+4 *A+4
*A-4 *
A-8
Fan speed MANUAL in starting
Fan speed AUTO in stability and stability
L
L+
M
M+
H
W8
(L + M) / 2
WB
(M + H) / 2
WE
Indication Fan speed
Fan speed setup
HEAT
ON
AUTO
YES
NO
MANUAL
TC 42°C
W
Min air flow rate control
Tc
51
50
42
41
M+ (WC)
* Fan spee
d
=
(TC – (41+a)) / (51 41) x (M+ L ) + L
N
o
limi
t
*
*
1: Fan speed = (M + -L+) x 1 5 + L+
*
2: Fan speed = (M + -L+) x 2 5 + L+
*
3: Fan speed = (M + -L+) x 3 5 + L+
(Calculated with linear approximation from M+ and L+)
5) In order to prevent Cold draft when
compressor step during heating
operation. Then louver will move to
upper position and fan speed will
reduce or off.
FILE NO. SVM-14017
Quiet
5
*
4
4: Fan speed = (M + -L+) x 4 5 + L+
*