− 71 −
FILE NO. SVM-04004
9-6-3. How to shorten time of restart delay timer
1 Press [CLR] button while pressing [CHECK] button
with a tip of a pencil.
2 Then press [START/STOP] button to transmit the
signal to the indoor unit.
Table 9-6-3 Approximate resistance value of thermo sensor
Temperature 0°C 10°C 20°C 25°C 30°C
Resistance value 33.8 20.35 12.59 10.00 7.99
(kΩ)
PRESET
FAN MODE
Hi-POWER
ON
OFF SET CLR
ECO
AUTO
TIMER
CLOCK CHECKRESET
FILTER
FIX
SWING
MEMO
START/STOP
17
1
2
A
B
AUTOA
9-6-4. How to set/cancel the self cleaning function
The self cleaning function is set from a factory. To cancel this function, should keep press the
temporary switch for 20 seconds till can hear the long combination sound and repeat the same
procedure when need to set.