– 17 –
FILE NO. SVM-02001
5-3. RAS-10UKHP-E / RAS-10UAH-E
Indoor unit
Cross flow fan
Cooling
Heating
4-way valve
Heating
Cooling
Compressor
Condenser
Propeller fan
Outdoor unit
PH120T1-4C
Cooling
Heating
Mark( )means check points of Gas Leak.
O.D.:9.52mm O.D.:6.35mm
Cooling
Heating
Packed valve
(∅9.52)
Packed valve
(∅6.35)
0.39m
(Connecting pipe)
∅9.52
0.49m
(Connecting pipe)
∅6.35
T1
P
Refrigerant
R-22 : 0.74 kg.
Capillary tube
∅1.7x1600
Accumulator
Evaporator
Standard 1.55 40.0 High 20/– 7/6
Heating Overload*1 1.9 ~ 2.1 52.0 ~ 59.0 Low 27/– 24/18
Low temperature 1.3 35.0 High 20/––10/–10
Standard 1.94 12.0 High 27/19 35/24
Cooling Overload 2.50 15.0 High 32/23 43/26
Low temperature 0.32 2.0 Low 21/15 21/15
Note :
• Measure the heat exchanger temperature at the center of U-bend. (By means of TC sensor)
*1 • During heating overload operation, a value for the high temperature limit control operation is included.
50Hz
Standard
pressure P
(MPaG)
Surface temp. of heat
exchanger interchanging
pipe T1 (°C)
Fan speed
(indoor)
Ambient temp.
conditions DB/WB
(°C)
Indoor Outdoor