5-2. RAS-10UKH-ES3 / RAS-10UAH-ES3
Indoor unit
Cross flow fan
Cooling
Heating
4-way valve
Heating
Cooling
Compressor
Condenser
Propeller fan
Outdoor unit
PA108X1T-4FZ1
Cooling
Heating
Mark ( ) means check points of Gas Leak.
O.D.:9.52 mm O.D.:6.35 mm
Cooling
Heating
Packed valve
(9.52)
Packed valve
(6.35)
0.39 m
(Connecting pipe)
9.52
0.49 m
(Connecting pipe)
6.35
T1
P
Refrigerant
R410a : 0.70 kg.
Capillary tube
1.0 x 1300
l
Accumulator
Evaporator
Ambient temp.
conditions DB/WB
(°C)
Indoor Outdoor
Standard 2.45 40.0 High 20/15 7/6
Heating Overload 3.45 52.0 Low 27/ 24/18
Low temperature 2.10 35.0 High 20/––10/10
Standard 0.90 11.0 High 27/19 35/24
Cooling Overload 1.07 16.0 High 32/23 43/26
Low temperature 0.85 5.0 Low 21/15 21/15
Standard
pressure
P
(MPaG)
Surface temp. of heat
exchanger interchanging
pipe
T1
(°C)
Fan speed
(indoor)
50Hz
Note
Measure the heat exchanger temperature at the center of U-bend. (By means of TC sensor)
FILE NO. SVM-04017
Capillary tube
1.2 x 600
l