- 18 -
4-3. Outdoor Unit (RAS-10UAH-E3)
No. Parts name Type Specifications
Output (Rated) 750 W, 2 poles, 1 phase, 220 - 240 V, 50Hz
1 Compressor PH120T1-4C Winding resistance ( ) C-R C-S
(at 20 C) 4.53 8.73
Output (Rated) 20 W, 6 poles, 1 phase, 220 - 240 V, 50Hz
2 Fan motor (for outdoor)
HF-240-20B or
Winding resistance ( ) Red-Black White-Black
(at 20 C
3
Running capacitor
DS451155BPQC AC 450 V, 1.5mF
(for fan motor)
W
W
°
°
4
Running capacitor
DS371256CPNB AC 370 V, 25mF
(for compressor)
5 Overload relay JMRA99269-9200 U/T : 6.8A (90
C), OPEN : 135±5 C, CLOSE : 69±11 C
°
° °
No. Parts name Type Specifications
Output (Rated) 560W, 2poles, 1 phase, 220 240V, 50Hz
1 Compressor PH80T1-4C Winding resistance () C-R C-S
(at 20°C) 4.80 8.37
Output (Rated) 20W, 6poles, 1 phase, 220 240V, 50Hz
2 Fan motor (for outdoor)
HF-240-20B or
SKF-240-20B
Winding resistance () Red-Black White-Black
(at 20°C)
387.3 or 235.2
466.2 or 260.1
3
Running capacitor
DS451155CBPQC AC 450V, 1.5F
(for fan motor)
4
Running capacitor
DS371256CPN AC 370V, 25F
(for compressor)
5 Overload relay JMRA99208-9201 U/T: 4.2A (80°C), OPEN: 135±5°C, CLOSE: 69±11°C
4-4. Outdoor Unit (RAS-07UAH-E3)
FILE NO. SVM-04004
SKF-240-20B
387.3 or 235.2 466.2 or 260.1

Table of Contents