FILE NO. SVM-10015
7-2. Operation Data
<Coolin
g
>
Tempeature Model name Standard Heat exchanger Indoor Outdoor Compressor
condition(°C) RAS- pressure pipe temp. fan mode fan mode revolution
Indoor Outdoor P (MPa) T1 (°C) T2 (°C) (rps)
27/19 35/- 137SKV-E3 0.8 to 1.0 11 to 13 46 to 48 High High 79
167SKV-E3 0.7
to 0.9 10 to 12 40 to 42 High High 89
<Heating>
Tempeature Model name Standard Heat exchanger Indoor Outdoor Compressor
condition(°C) RAS- pressure pipe temp. fan mode fan mode revolution
Indoor Outdoor P (MPa) T1 (°C) T2 (°C) (rps)
20/- 7/6 137SKV-E3 2.6 to 2.8 41 to 43 0 to 2 High High 83
167SKV-E3 2.5
to 2.7 44 to 46 0 to 3 High High 86
NOTES :
1. Measure surface temperature of heat exchanger pipe around center of heat exchaner path U bent.
(Thermistor themometer)
2. Connecting piping condition : 5 m