<Inspection procedure>
1. Remove the front panel. (Remove 2 screws.)
2. Remove the cover of the fan motor lead wires.
3.
Check AC voltage with CN10 connector while the fan motor is rotating.
NOTE :
Using a tester, measure the resistance value of each winding coil.
Use a thin test rod.
1
3
5
1
2
3
2
1
3
2
1
3
2
1
3
2
1
3
CN10
CN11
P.C. board
WHI
BLK
RED
BRW
GRY
YEL
(For AC fan motor)
Do not disconnect the connector while the fan motor is rotating.
For P.C. board side, proceed to the item "Only indoor fan does not operate"
of "Judgment of Trouble by Every Symptom".
SJM-240-25 (RAS-05, 07, 10, 13)
SJM-240-35 (RAS-16)
Resistance value (RAS-05, 07, 10, 13)
Position (P.C. board)
Between 3 (Black) - 1 (Red)
Between 3 (Black) - 5 (White)
Between 1 (Red) - 5 (White)
120.6
±
8.4
244.2
±
17
364.8
±
25.5
Resistance value (RAS-16)
115.6
±
8.
146.2
±
1
0.2
261.8
±
18.3
FILE NO. SVM-16030