FILE NO. SVM-05016
4-5. Outdoor Unit (RAS-24UA-E4, RAS-24UAX4, RAS-24UAX3-T1
4-6. Outdoor Unit (RAS-24UA-AR4)
18
No. Parts name Type Specifications
Output (Rated) 2200 W, 2 poles, 1 phase, 220 240 V, 50 Hz
1 Compressor PH400X3CS-4KT1 Winding resistance ( ) C-R C-S
(at 20 °C)
Output (Rated) 65 W, 6 poles, 1 phase, 220 240 V, 50 Hz
Winding resistance ( ) Red-Black White-Black
2 Fan motor (for outdoor)
(at 20 °C) 64.4 127.4
KFG6-71SB5P-T
AC 440 V, 45µF
1.13
2.10
3
Running capacitor
451355L
AC 450 V, 3.5µF
(for fan motor)
BUM44X4505B
4
5 Magnetic contactor
A35
220 240 V, 50 Hz
Running capacitor
(for compressor)
SK42CMP60U1-S
AC 450 V, 3.5µF
No. Parts name Type Specifications
Output (Rated) 2200 W, 2 poles, 1 phase, 220 240 V, 50 Hz
1 Compressor PH400X3CS-4KTS1 Winding resistance ( )
C-R
C-S
(at 20 °C) 1.01
2.32
Output (Rated) 65 W, 6 poles, 1 phase, 220 240 V, 50 Hz
2 Fan motor (for outdoor)
MMF-230-65I
Winding resistance ( ) Red-Black White-Black
(at 20 °C)
71.2 139.0
3
Running capacitor
451305L
(for fan motor)
4
Running capacitor
AC 420 V, 60µF
(for compressor)
5 Magnetic contactor
A35
220 240 V, 50 Hz

Table of Contents