FILE NO. SVM-02008
– 20 –
5-3. RAS-18UFP-AR / RAS-18UA-AR
Note : Measure the heat exchanger temperature at the center of U-bend. (By means of TC sensor.)
Standard 0.4 10.0 High 27/19 35/24
Cooling High temperature 0.5 13.0 High 32/23 43/26
Low temperature 0.3 2.0 Low 21/15 21/15
50Hz
Fan speed
(indoor)
Ambient temp.
conditions DB/WB
(°C)
Indoor Outdoor
Standard
pressure P
(MPaG)
Surface temp. of heat
exchanger interchanging
pipe T (°C)
Indoor unit
Multi blade fan
Compressor
Condenser
Propeller fan
Outdoor unit
PH250X3-4LM
O.D.:6.35 mm
Packed valve
(∅12.70)
Packed valve
T
P
Refrigerant
R-22 1.17 kg
Evaporator
Capillary tube
∅
2.0x1000
S
Capillary tube
∅
0.8x900
S
Muffler
0.49m
(Connecting pipe)
∅6.35 mm
Mark ( ) means check points of Gas Leak
O.D.:12.70 mm
0.39m
(Connecting pipe)
∅12.70 mm
∅12.70 mm
0.39m
(Flexible pipe)
(∅6.35)