28
FILE NO. SVM-03010(1)
5-6.RAS-18UKPX2 / RAS-18UAX2
Indoor unit
Cross flow fan
Compressor
Condenser
Propeller fan
Outdoor unit
2JS350DJSM486
O.D.:12.7 mm
O.D.:6.35 mm
Packed valve
(12.7)
Packed valve
(6.35)
T
P
Refrigerant
R22 1.0 kg
Evaporator
0.39 m
(Connecting pipe)
12.7
0.49 m
(Connecting pipe)
6.35
Mark ( ) means check points of Gas Leak
Capillary tube
2.0x600 s
Note : Measure the heat exchanger temperature at the center of U-bend. (By means of TC sensor.)
Ambient temp.
conditions DB/WB
(°C)
Indoor Outdoor
Standard 0.4 11.0 High 27/19 35/24
Cooling High temperature 0.5 13.0 High 32/23 43/26
Low temperature 0.3 2.0 Low 21/15 21/15
Fan speed
(indoor)
50 Hz
Standard
pressure
P
(MPaG)
Surface temp. of heat
exchanger interchanging
pipe
T
(°C)