5. REFRIGERATION CYCLE DIAGRAM
5-1. RAS-18GFHP-ES2 / RAS-18GAH-ES2
Standard 2.7 45.0 High 20/– 7/6
Heating High temperature*1 3.0 ~ 3.8 49.0 ~ 58.0 Low 27/– 24/18
Low temperature 2.0 34.0 High 20/– –10/–10
Standard 0.9 10.0 High 27/19 35/24
Cooling High temperature 1.0 15.0 High 32/23 43/26
Low temperature 0.6 1.0 Low 21/15 21/15
Note : Measure the heat exchanger temperature at the center of U-bend. (By means of TC sensor.)
*1 : During heating overload, the high temperature limit control operation is included.
50Hz
Standard
pressure P
(MPaG)
Surface temp. of heat
exchanger interchanging
pipe T (°C)
Fan speed
(indoor)
Ambient temp.
conditions DB/WB
(°C)
Indoor Outdoor
Evaporator
Indoor unit
Multi blade fan
Cooling
Heating
Muffler
4-way valve
Heating
Cooling
Compressor
Condenser
Propeller fan
Outdoor unit
Capillary tube
∅2.0x1200S
P225X2CS-4KU1
Accumulator
Cooling
Heating
O.D.:6.35 mm
Packed valve
0.49m
(Connecting pipe)
∅6.35 mm
T
Refrigerant
R-410A 1.15 Kg
Mark ( ) means check points of Gas Leak
Packed valve
(∅12.70)
P
O.D.:12.70 mm
0.39m
(Connecting pipe)
∅12.70 mm
∅12.70 mm
0.39m
(Flexible pipe)
Cooling
Heating
(∅6.35)