FILE NO. SVM-06020
5-3. RAS-24GKP-ES2 / RAS-24GA-ES2
Note :
Measure the heat exchanger temperature at the center of U-bend. (By means of TC sensor)
Ambient temp.
conditions DB/WB
(° C)
Indoor Outdoor
Standard 3.183 7.0 High 27/19 35/24
Cooling Overload 4.040 11.7 High 32/23 43/26
Low temperature 1.651 -0.4 Low 21/15 21/15
Fan speed
(indoor)
50Hz
Standard
pressure
P
(MPaG)
Surface temp. of heat
exchanger interchanging
pipe
T1
(° C)
Heat exchanger
Indoor unit
Cross flow fan
Compressor
Condenser
Propeller fan
Outdoor unit
PA290X3CS-4MU1
Cooling
Mark(
)means check points of Gas Leak.
O.D.:12.7mm
O.D.:6.35mm
Cooling
Packed valve
Gas container connection (Reinstall etc.)
(
12.7)
Packed valve
(
6.35)
0.39m
(Connecting pipe)
12.7
0.49m
(Connecting pipe)
6.35
T1
P
Refrigerant
R410A 1.70kg
Capillary tube
2.0x900
s
Cooling
Accumulator
- 17 -