8-6-4. Remote Controller A or B Selection
Setting
When two indoor units are installed in the separated rooms, it
is not necessary to change the selector switches.
<Remote control A or B Selection>
When two indoor units are installed in the same room or
adjacent two rooms, if operating a unit, two units may receive
the remote control signal simultaneously and operate. In this
case, the operation can be preserved by setting either one
indoor unit or remote control to B setting. (Both are set to A
setting in factory shipment.)
The remote control signal is not received when the settings of
indoor unit and remote control are different.
There is no relation between A setting/B setting and A room/B
room when connecting the piping and cables.
<Remote Control A-B Selection>
To separate using of remote control for each indoor unit in case
of 2 air conditioner are installed nearly.
the remote control signal simultaneously and operate. In this
Remote Control B Setup.
1. Press RESET button on the indoor unit to turn the air conditioner ON.
2
. Point the remote control at the indoor unit.
3. Push and hold CHK button on the Remote Control by the tip of the
pencil. "00" will be shown on the display.
4. Press MODE during pushing CHK , "B" will show on the display
and"00" will disappear and the air conditioner will turn OFF. The
Remote Control B is memorized.
Note : 1. Repeat above step to reset Remote Control to be A.
2
. Remote Control A have not "A" display.
3. Detault setting of Remote Control from factory is A.
Fig. 8-6-4
SLEEP
PRESET
ONE-TOUCH
FAN
QUIET
SWING
CHK
FILTER
CLOCK
TIMER
FIX Hi-POWER ECO
COMFORT
SELECT
MODE
ON OFF
SET
CLR
B Display
00 Display
The product was shipped with Auto Restart
Turn it ON as required.
function in the OFF position.
Information
FILE NO. SVM-10049
45
RESET
Hi P OW E R F IL T E R P AP T IME R O P E R AT IO N
RESET button
<How to Set the Auto Restart>
1. Press and hold the RESET button on the indoor unit for 3
seconds to set the operation. (3 beep sound and
OPERATION lamp blink 5 time/sec for 5 seconds)
2. Press and hold the RESET button on the indoor unit for 3
seconds to cancel the operation. (3 beep sound but
OPERATION lamp does not blink)
In case of ON timer or OFF timer are set, AUTO RESTART
OPERATION does not activate.
To switch the TEST RUN (COOL) mode, press RESET
8-6-2. Test Operation
button for 10 seconds (The beeper will make a short beep).
Fig. 8-6-3
This product is designed so that, after a power failure, it
8-6-3. Auto Restart Setting
can restart automatically in the same operating mode as
before the power failure.