– 93 –
11-9-3. Indoor Unit (Other Parts)
11-9-4. Outdoor Unit
No.
1
Part name
Room temp. (TA) sensor
Heat exchanger (TC) sensor
Checking procedure
Disconnect the connector and measure the resistance value with tester.
(Normal temp.)
No.
1
Part name
Compressor
(Model : DA130A1F-27F)
Checking procedure
Measure the resistance value of winding by using the tester.
Red
White Black
Red
White Black
Measure the resistance value of winding by using the tester.
Resistance value
1435 ± 144.
Under 20°C
Measure the resistance value of winding by using the tester.
Temperature
Sensor
TA, TC,TCJ (k. )
10°C 20°C 25°C 30°C 40°C
20.7 12.6 10.0 7.9 4.5
5
4
3
2
1
White
Yellow
Yellow
Yellow
Yellow
5
4
3
2
1
Refer to 11-5-1. (5).
Measure the resistance value of each winding coil by using the tester.
(Under normal temp. 25°C)
Position
1 to 2
1 to 3
1 to 4
1 to 5
Resistance value
250 ± 20.
Refer to 11-5-1. (3) and (4).
2
3
Remote controller
Louver motor & Damper motor
MP24Z3T
4
Indoor fan motor
Measure the resistance value of each winding by using the tester.
Position
Red - White
White - Black
Black - Red
Resistance value
0.92 to 1.02Ω
ı
Under 20ºC
DA130A1F-27F
DA89X1C-1F-23FZ
1.04 to 1.16Ω
Position
Red - White
White - Black
Black- Red
Resistance value
20 to 22.
20 to 22.
20 to 22.
2
3
4
Outdoor fan motor
(Model : ICF-140-43-4R)
4-way valve coil
(Model : STF-01AJ646A1)
Pulse motor valve coil
CAM-MD12TF-16
Position
Red-White
Red-Orange
Red-Yellow
Red-Blue
CAM-MD12TF-10
Position
Red-White
Red-Orange
Brown-Yellow
Brown-Blue
Resistance value
42 to 50Ω
42 to 50Ω
42 to 50Ω
42 to 50Ω
42 to 50Ω
42 to 50Ω
42 to 50Ω
42 to 50Ω
RAS-18SAV-E, RAS-18SAV2-E
(
Model : DA89X1C-23FZ2)
RAS-10SAV2-E, RAS-13SAV2-E
Heat exchanger (TCJ)sensor
ICF-340-41-1
(Model : CAM-MD12TF-16)
or
(Model : CAM-MD12TF-10)
RAS-18SAV-E
Resistance value