8-3. TEMPORARY Operation
Setting the TEMPORARY switch to AUTO starts
the automatic operation, to COOL starts the
cooling operation (LOW), respectively.
Setting the TEMPORARY switch to AUTO or
COOL, the operation cant be performed from the
remote controller. (without STOP button)
Temporary Auto Operation is operated with the set
temperature fixed at 24°C.
Temporary Cooling Operation is operated with
Indoor fan speed fixed to Low and with compressor
motor speed fixed to 28.0Hz.
*
1 If the float switch is not reset (closed) within 2 minutes 30 seconds, the operation lamp flashes. (5Hz)
*
2 When the float switch is reset, the following phenomena appear.
The operation lamp stops flashing and keeps lighting.
The outdoor unit is reactivated 2 minutes and 30 seconds after.
Fig. 8-4-2
Thermo OFF Thermo ON
Drain pump
ON
ON
Float switch
CLOSE
Compressor
ON OFF ON
Indoor fan
ON
Operation starts
Drain pump
ON
Float switch
OPEN
Compressor
OFF
Indoor fan
Compressor stops.
Drain pump continues operation.
Operation starts at overflowing Overflow detection durling operation
ON
Overflow detection
ON ON
CLOSE OPEN CLOSE
ON ONOFF
ON
Overflow stops
*
1
2'30"
*
2
2'30"
To stop the temporary operation,
set the switch to AUTO RESTART OFF.
Fig. 8-3-1
8-4. Control of Drain-up Kit (Option)
8-4-1. Dain Control
In cooling, and dry operation, drain pump is
actuated to drain up.
[OPERATION CONTROL]
During cooling, and drying operation :
Drain pump ON.
Fig. 8-4-1
8-4-2. Over Flow Check Control
Drain level is checked by float switch. If the float switch is actuated (OPEN), stop operation of the outdoor unit
and operate the drain pump exert to drain out.
In fan only, heating operation (Heat pump model only), and even in stoppage but while float switch is actuated,
drain pump is ON (Operation).
[OVERFLOW CHECK AND CONTROL]