Outdoor Unit : RAS-3M26YAV-E
<Heating>
NOTE :
Model of Indoor unit 10 : RAS-M10UKV-E3, 13 : RAS-M13UKV-E3, 16 : RAS-M16UKV-E3
MCA : Minimum Circuit Amps.
ICF : Maximum Instantaneous Current Flow (Equivalent to MCA in case of inverter air conditioner)
MOCP: Maximum Overcurrent Protection (Fuse only)
MSC : Maximum Starting Current
FLA : Full Load Amps.
RLA : Rated Load Amps. RLA under conditions on the right.
DB WB
Indoor temp. (°C) 20
Outdoor temp. (°C) 7 6
System Compressor Fan motor FLA
Voltage range Power supply
Combination of
indoor unit operation
Hz
Volts-
Ph.
Min. Max. MCA ICF
MOCP
(Amps)
MSC RLA Indoor Outdoor
10 –– 8.15 8.15 20 6.00 6.00 0.15 x 1 = 0.15 0.5
13 –– 11.20 11.20 20 8.44 8.44 0.15 x 1 = 0.15 0.5
1 unit
16 –– 13.15 13.15 20 10.00 10.00 0.15 x 1 = 0.15 0.5
10 10 11.16 11.16 20 8.29 8.29 0.15 x 2 = 0.30 0.5
13 10 12.23 12.23 20 9.14 9.14 0.15 x 2 = 0.30 0.5
16 10 13.00 13.00 20 9.76 9.76 0.15 x 2 = 0.30 0.5
13 13 13.00 13.00 20 9.76 9.76 0.15 x 2 = 0.30 0.5
16 13 14.00 14.00 20 10.56 10.56 0.15 x 2 = 0.30 0.5
2 units
16 16 14.78 14.78 20 11.18 11.18 0.15 x 2 = 0.30 0.5
10 10 10 12.51 12.51 20 9.25 9.25 0.15 x 3 = 0.45 0.5
13 10 10 12.85 12.85 20 9.52 9.52 0.15 x 3 = 0.45 0.5
16 10 10 13.24 13.24 20 9.83 9.83 0.15 x 3 = 0.45 0.5
13 13 10 13.24 13.24 20 9.83 9.83 0.15 x 3 = 0.45 0.5
16 13 10 13.24 13.24 20 9.83 9.83 0.15 x 3 = 0.45 0.5
13 13 13 13.24 13.24 20 9.83 9.83 0.15 x 3 = 0.45 0.5
16 16 10 13.58 13.58 20 10.10 10.10 0.15 x 3 = 0.45 0.5
16 13 13 13.58 13.58 20 10.10 10.10 0.15 x 3 = 0.45 0.5
3 units
16 16 13
50 or 60 2301 198 264
13.90 13.90 20 10.36 10.36 0.15 x 3 = 0.45 0.5