Toshiba RAS-M16UKCV-E - 6-2. Operation Performance Data

Toshiba RAS-M16UKCV-E
86 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
– 21 –
6-2. Operation Data
NOTE :
Model of Indoor unit 10 : RAS-M10UKCV-E, 13 : RAS-M13UKCV-E, 16 : RAS-M16UKCV-E
NOTES :
(1) Measure surface temperature of heat exchanger pipe around center of heat exchanger path U bent.
(Thermistor themometer)
(2) Connecting piping condition : 5 meters x 3 units (5m / each unit)
Temperature
No. of
condition (°C)
operating
Indoor Outdoor
units
1 unit
2 units
27/19 35/–
3 units
Combinations
of indoor units
10
13
16
10 10
13 10
16 10
13 13
16 13
16 16
10 10 10
13 10 10
16 10 10
13 13 10
Standard
Surface temp. of
pressure
heat exchanger
P (Mpa)
T1 (°C) T2 (°C)
0,92 11 42
0,85 9 47
0,73 8 50
0,96 10,5 to 11,5 49
0,92 11 to 12 51
0,92 11 to 12 51
0,92 11 to 12 51
0,92 11 to 12 51
0,92 11 to 12 51
1,04 12,5 to 13,5 51
0,98 12 to 13 52
0,98 12 to 13 52
0,98 12 to 13 52
Fan speed
Compressor
revolution
Indoor Outdoor
(rps)
High Med. 37
High High 57
High High 73
High High 69
High High 78
High High 78
High High 78
High High 78
High High 78
High High 81
High High 89
High High 89
High High 89