–23–
Address is displayed here.
Address is displayed here.
6 Push the [ MENU] button to set the other
Code (DN) and Data. After “Continue?” is
displayed on the screen, push the
Yes” [
F1] button.
Indoor address change
Change “Code (DN)” from [0010] to [0013] with
the [
] / [ ] button.
Change “Data” from [0003] to [0002] with the
[
] / [ ] button.
7 Push the [ MENU] button to set the other
Code (DN) and Data. After “Continue?” is
displayed on the screen, push the
Yes” [
F1] button.
Group address change
Change “Code (DN)” from [0010] to [0014] with
the [
] / [ ] button.
Change “Data” from [0001] to [0002] with the
[ ] / [ ] button.
8 Push the [ MENU] button to set the other
Code (DN) and Data. After “Continue?” is
displayed on the screen, push the
No” [ F2] button to finish the
setting operation. “
Setting” appears on
the screen for a while, then the screen
returns to the “Field setting menu” screen.
Pushing the “ No” [ F2] button
displays the unit selection screen when the
group control is used. Push the [ CANCEL]
button on the unit selection screen to finish the
setting operation. “ Setting” appears on the
screen for a while, then the screen returns to the
“Field setting menu” screen.
DN setting
Code
Data
3-3
Return
0013 0003
Fix
<>
(DN) I.DN
DN setting
Code
Data
3-3
Return Fix
<>
00020013
(DN) I.DN
DN setting
Code
Data
3-3
Return
0014 0001
Fix
<>
(DN) I.DN
DN setting
Code
Data
3-3
Return Fix
<>
0002
0014
(DN) I.DN
Yes
Yes
No
No
9 Test run
Before test run
Before turning on the power supply, carry out the following procedure.
1) By using tester (500 VMΩ), check that resistance of 1 MΩ or more exists between the terminal block 1 to
3 and the earth (grounding).
If resistance of less than 1 MΩ is detected, do not run the unit.
2) Check the valve of the outdoor unit being opened fully.
To protect the compressor at activation time, leave power-ON for 12 hours or more before operating.
Execute a test run
Operate the unit with the remote controller as usual.
For the procedure of the operation, refer to the attached Owner’s Manual.
A forced test run can be executed in the following procedure even if the operation stops by thermostat-OFF.
In order to prevent a serial operation, the forced test run is released after 60 minutes have passed and returns to
the usual operation.
CAUTION
Do not use the forced test run for cases other than the test run because it applies an excessive load to the devices.
Be careful of fan operation when the circuit breaker is turned on. If the refrigerant leak detection sensor detects the
refrigerant leak, a fan automatically rotates even while an air conditioner stops. Be careful not to be injured by the fan.
1 Push the [ MENU] button to display the
menu screen.
2 Push and hold the [ MENU] button and
the [
] button at the same time to
display the “Field setting menu”.
Push and hold the buttons for more than 4
seconds.
3 Push the [ ] / [ ] button to select
“1. Test mode” on the “Field setting menu”
screen, then push the “ Set” [
F2] button.
Pushing the “ Yes” [ F1] button
sets the test mode and the screen returns to the
“Field setting menu” screen.
Push [ CANCEL] twice, the screen (2)
appears.
1.Test mode
2.Register service info.
3.Alarm history
4.Monitor function
5.Setting louver position
Field setting menu(1/2)
Return
Set
1.Test mode
2.Register service info.
3.Alarm history
4.Monitor function
5.Setting louver position
Field setting menu(1/2)
Return
Set
Set
Yes
Return
Test mode start.
NoYes
Test mode
45-EN 46-EN