ELECTRICAL CONNECTION
WARNING
Use the specied wires for wiring connect the terminals. Securely x them to prevent
external forces applied to the terminals from affecting the terminals.
Incomplete connection or xation may cause a re or other trouble.
Connect earth wire. (grounding work)
Incomplete grounding cause an electric shock.
Do not connect earth wires to gas pipes, water pipes, lightning conductor or telephone earth wires.
Appliance shall be installed in accordance with national wiring regulations.
Capacity shortage of power circuit or incomplete installation may cause an electric shock or a re.
Under no circumstances, the power supply wire or the indoor and outdoor connecting wire
must not be connected in the middle (Connection using a solderless terminal etc.)
Connection trouble in the places where the wire is connected in the middle may give rise to smoking
and/or a re.
CAUTION
For power supply specications, follow the Installation Manual of outdoor unit.
Do not connect 220 – 240V power to the terminal blocks (
A
,
B
) for control wiring.
Otherwise, the system will fail.
Do not damage or scratch the conductive core and inner insulator of power and Indoor / Outdoor
connecting wires while peeling them.
Perform the electric wiring so that it does not come to contact with the high-temperature part of the
pipe.
The coating may melt resulting in an accident.
Do not turn on the power of the indoor unit until vacuuming of the refrigerant pipes completes.
Wiring specications
Indoor / Outdoor connecting wires specications
Indoor unit power supplied from outdoor unit
The outdoor unit power supply patterns vary on models.
Indoor unit power supply
1~50 Hz 220 - 240V
1~60 Hz 220V
Indoor / Outdoor connecting wires*
4 × 1.5 mm² or more
(H07RN-F or 60245 IEC 66)*
Up to 70 m
*Number of wire × wire size
*Including earth line
Remote controller wiring
Remote controller wiring, remote controller inter-unit
wiring
Wire size: 2 × 0.5 to 2.0 mm²
Total wire length of remote controller wiring and
remote controller inter-unit wiring
= L + L1 + L2 + … Ln
In case of wired type only Up to 500 m
2 remote controllers Up to 300 m
In case of wireless type included Up to 400 m
Total wire length of remote controller inter-unit wiring = L1 + L2 + … Ln Up to 200 m
* The remote controller wiring length differs depending on the remote controller used. For details, refer to the
Installation Manual attached to the remote controller.