Installation Manual
32
32-EN
Remote controller sensor
The temperature sensor of the indoor unit
senses room temperature usually. Set the remote
controller sensor to sense the temperature around
the remote controller.
Select items following the basic operation
procedure (
1
2
3
4
5
6
7 ).
• Specify
[32] for the Code No. in Procedure 4.
Select the following data for the set data in
Procedure
5.
Set data Remote controller sensor
0000 Not in use (Factory default)
0001 In use
When ashes, the remote controller sensor is
defective.
Select the set data [0000] (not in use) or replace
the remote controller.
Communication type
When connecting to the central control device
dedicated to TCC-Link, it is necessary to change
to TCC-Link.
Follow to the basic opreration procedure
(
1
2
3
4
5
6
7 ).
• Specify
[FC] for the Code No. in Procedure 4.
Select the set data [0000] (TCC-Link) in
Procedure
5.
Set data Communication type
0000 TCC-Link
0004 TU2C-Link (Factory default)
Fan speed setting when
thermostat-OFF in cooling mode
Set the fan speed when the room temperature
reaches the set temperature in the cooling mode.
Follow to the basic opreration procedure
(
1
2
3
4
5
6
7 ).
• Specify
[9A] for the Code No. in Procedure 4.
Select the following data for the set data in
Procedure
5.
Set data
Fan speed when thermostat-OFF
in cooling mode
0000 Remote controller setting
0001
Extremely low speed (UL)
(Factory default)
8°C operation
Pre-heating operation can be set for cold regions
where room temperature drops to below zero.
Follow to the basic opreration procedure
(
1
2
3
4
5
6
7 ).
• Specify
[d1] for the Code No. in Procedure 4.
Select the following data for the set data in
Procedure
5.
Set data 8°C Operation setting
0000 None (Factory default)
0001 8°C Operation setting
Installing optional parts
When installing optional parts, data setup may be
required with remote controller.
Be sure to set the data, according to Installation
Manual for optional parts.
Information
The following functions require a connection
with the RBC-AMTU
½½½
and RBC-AMSU
½½½
remote controller. For details, refer to the manual
included with the remote controller.
Individual unit selection during group operation
Individual setting of louver position (wind
direction)
Swing type setting
Louver lock (no swing) setting
Energy saving operation (Power saving
operation)
• Notication of lter cleaning time
Others
The following functions can be used with this
model.
Refer to the Service Manual for more information.
Rotation / backup operation
• Free cooling
• Secondary heating
• Power shift