Installation Manual
43
43-EN
In case of wireless remote controller
(Forced test operation is performed in a
different way.)
REQUIREMENT
For the operation procedure, be sure to follow
the Owner’s Manual.
Finish the forced cooling operation in a short
time because it applies excessive strength to
the air conditioner.
A test operation of forced heating is
unavailable. Perform a test operation by
heating operation using the switches of the
remote controller.
However heating operation may be not
carried out according to the temperature
conditions.
Check wiring/piping of indoor and outdoor
units
1. When pushing [RESET] button for 10
seconds or more, “Pi!” sound is heard and
the operation changes to a forced cooling
operation. After approx. 3 minutes, a
cooling operation starts forcedly.
Check cool air starts blowing. If the
operation does not start, check wiring
again.
2. To stop a test operation, push [RESET]
button once again (Approx. 1 second).
The louver closes and the operation stops.
OPERATION /
RESET button
Check transmission of remote controller
1. Push “START/STOP” button of the remote
controller to check an operation can also
start by the remote controller.
“Cooling” operation by the remote
controller may be unavailable according
to the temperature conditions.
Check wiring/piping of the indoor and
outdoor units in forced cooling operation.
Indoor unit data
Code No. Data name
01 Room temperature (remote controller)
02 Indoor unit intake air temperature (TA)
03
Indoor unit heat exchanger (coil)
temperature (TCJ)
04
Indoor unit heat exchanger (coil)
temperature (TC)
07 Indoor unit fan speed (×1 rpm)
B9
Communication protocol
(0000: TCC-Link, 0001: TU2C-Link)
F3
Indoor unit fan cumulative operating
hours (×1 h)
F8 Indoor unit discharge air temperature *1
Outdoor unit data *2
Code No. Data name
60
Outdoor unit heat exchanger (coil)
temperature (TE)
61 Outside air temperature (TO)
62 Compressor discharge temperature (TD)
63 Compressor suction temperature (TS)
65 Heatsink temperature (THS)
6A Operating current (×1/10)
6D
Outdoor heat exchange (coil)
temperature (TL)
F1
Compressor cumulative operating hours
(×100 h)
*1 : The above temperature values are estimated from the
temperature of the heat exchanger. It may differ from the
actual discharge temperature.
*2 : For outdoor unit data, refer to the Installation Manual and
Service Manual of the outdoor unit.