– 45 –
< Procedure >
1 Push
TEST
button and temp. setup button
simultaneously for at least 4 seconds.
After a while, the display flashes as shown in the
figure. Confirm that the CODE No. is [01].
• If the CODE No. is not [01], push
TEST
button to
erase the display content, and repeat the
procedure from the beginning.
(No operation of the remote controller is accepted
for a while after
TEST
button is pushed.)
11. Specific Indoor Unit Priority Mode
2 Each time you push
UNIT LOUVER
button, indoor unit
numbers in the control group change cyclically.
Select the indoor unit you want to change settings
for.
The fan of the selected unit runs. You can confirm
the indoor unit for which you want to change
settings.
3 Using temp. setup / buttons, specify
CODE No. [
∗∗
].
4 Using timer time / buttons, select SET
DATA [
∗∗∗∗
].
5 Push
SET
button. When the display changes from
flashing to lit, the setup is completed.
• To change settings of another indoor unit, repeat
from Procedure 2.
• To change other settings of the selected indoor
unit, repeat from Procedure 3.
Use
SET
button to clear the settings.
To make settings after
SET
button was pushed,
repeat from Procedure 2.
6 When settings have been completed, push
TEST
button to determine the settings.
When
TEST
button is pushed, “SETTING” flashes and
then the display content disappears and the air
conditioner enters the normal stop mode.
(While “SETTING” is flashing, no operation of the
remote controller is accepted.)