RBP-RC001-E Installation & Owner's Manual
I/O function list
Digital Input functions
Function name
Setting
classification
Details
Initially set
terminal No.
No function Not set
Run/Stop input signal
All
Used to perform Run/Stop operations with external static signals.
(Note 1)
DI1
Stop input (pulse) Used to perform a Stop operation with an external pulse signal. Not set
Operation pattern input 1
Enabled when the remote controller is set to External.
Switch the remote controller operation pattern with a combination of
input signals of the operation pattern input.
DI2
Operation pattern input 2 DI3
Input of demand mode
(Note 2)
Used to enable demand from outside. Not set
Note 1: Run/Stop (static signal) can be changed to Run/Stop (pulses). For details, refer to “DN code setting (P. 41)” and “DN
code list (P. 51)”. If Stop input (pulse) is set, Run/Stop input functions as the Run input (pulse).
Note 2: The initial value for the demand setting value is “0”. Note that if you enable demand with an incorrect setting, the unit
will be stopped.
Digital Output functions
Function name
Setting
classification
Details
Initially set
terminal No.
No function Not set
Operating output (Signal)
All
GR outputs during operation. (Also output when the compressor is
stopped with capacity control.)
You can change the output method by setting “Level of operating
output”.*
DO1
Failure output
Output when GR detects a failure.
You can change the output method by setting “Level of failure output”.*
DO2
Operation pattern output 1
Outputs the operation pattern state with a combination of operation
pattern outputs.
Not set
Operation pattern output 2 Not set
Pattern interlock output1
Outputs the state of the pattern interlock output setting of the selected
operation pattern.
Not set
Pattern interlock output2 Not set
* For details, refer to “DN code setting (P. 41)” and “DN code list (P. 51)”.