EasyManua.ls Logo

Toshiba RemotEye 4 - Page 130

Toshiba RemotEye 4
262 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
130 RemotEye 4 User Manual 90988-007
MODBUS (3X) INPUT REGISTERS 4300, 4400, AND 5000 SERIES PLATFORMS
Registers
Data Type
Description
Units
4300
4400
5000 N3R
5000 3P1
Multi
Supp
Multi
Supp
Multi
Supp
Multi
Supp
30818
Unsigned Integer
UPS History Total Number Operation Mode Change
Times
X 1
Y
X 1
Y
X 1
Y
X 1
Y
30819
Unsigned Integer
UPS History Total Number Warnings
Times
N/A
N/A
N/A
N/A
N/A
N/A
X 1
Y
30820
Unsigned Integer
UPS History Total Number System Settings Changed
Times
N/A
N/A
N/A
N/A
N/A
N/A
X 1
Y
30821
Unsigned Integer
UPS History Total Number Resets
Times
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
….
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
…..
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
30850
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
UPS Status
30851
Signed Integer
Fan 1 Speed
RPM
N/A
N/A
N/A
N/A
X1
Y
N/A
N/A
30852
Signed Integer
Fan 2 Speed
RPM
N/A
N/A
N/A
N/A
X1
Y
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
….
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
…..
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
30900
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
Note: The Modbus registers table style addressing is protocol base 0. If monitoring software uses PLC style addressing base 1, add one to the register number. For
example, Modbus address 30001 becomes PLC address 30002 ; address 10001 becomes PLC address 10002.
Note 2: Please make sure the latest RemotEye 4 firmware revision is installed in order to use the Modbus register table below. If not, there will be inconsistencies
between RemotEye 4 internal register addressing and this manual. Go to www.toshibaups.com to get the latest RemotEye 4 firmware.
Note 3: There are some parameters that take two Modbus registers to display the correct data, since one register can only go up to 65536 (2^16). Use the following
formula (with example) to calculate the correct value: (Register 1* 0x10000) + Register 2 = Correct Unit Value
e.g. (Register (30276) * 0x10000) + Register (30277) = Correct Value in Watts

Table of Contents

Other manuals for Toshiba RemotEye 4

Related product manuals