182 RemotEye 4 User Manual 90988-007
D.2 BACNET BINARY INPUT POINT MAPPING FOR 4400
ALL BACnet Object: Binary Input BACnet Property: Present Value Out of Service: FALSE
Access: Read Only Status Flags: Normal
4400 BACnet Binary Input Point Mapping
Inst. ID
Object Name & Description
Units
Comments
RMTI
-
4
Status
1
RemotEye 4 Data Link
True/False (1/0)
0 = Link Up; 1 = Link Down
2
RemotEye 4 Network Link
True/False (1/0)
0 = Link Up; 1 = Link Down
UPS Mode
3
Online Mode
True/False (1/0)
4
Backup Mode
True/False (1/0)
5
Bypass Mode
True/False (1/0)
6
Shutdown Mode
True/False (1/0)
7
Battery Test Mode
True/False (1/0)
8
Pre-Charge Mode
True/False (1/0)
9
Gate-Check Mode
True/False (1/0)
Battery Status
10
UPS Battery Status Unknown
True/False (1/0)
11
UPS Battery Status Normal
True/False (1/0)
12
UPS Battery Status Low
True/False (1/0)
13
UPS Battery Status Depleted
True/False (1/0)
14
UPS Battery Status Discharging
True/False (1/0)
15
UPS Battery Status Test Failure
True/False (1/0)
Battery Charge
Status
16
Protective Charging Set
True/False (1/0)
17
Equalized Charging Set
True/False (1/0)
18
Battery Charger Status Normal Charging
True/False (1/0)
19
Battery Charger Status Stop Charging
True/False (1/0)
20
Battery Charger Status Discharging
True/False (1/0)
Battery
Test
21
Battery Test Disabled
True/False (1/0)
22
Battery Test in Progress
True/False (1/0)