EasyManua.ls Logo

Toshiba RemotEye 4 - Appendix G- Bacnet Point Mapping for T1000; Bacnet Analog Input Point Mapping for T1000

Toshiba RemotEye 4
262 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
200 RemotEye 4 User Manual 90988-007
APPENDIX G BACNET POINT MAPPING FOR T1000
G.1 BACNET ANALOG INPUT POINT MAPPING FOR T1000
ALL BACnet Object: Analog Input BACnet Property: Present Value Out of Service: FALSE
Access: Read Only Status Flags: Normal
T1000 BACnet Analog Point Mapping
Inst. ID
Object Name & Description
Units
Comments
RMTI
-4 System
Information
1
RemotEye 4 Software Version
Firmware
Example: 1.00
2
RemotEye 4 Slave ID Number
ID
3
IP Address
IP Address
Example: 192.168.1.150
4
Subnet Mask
Subnet Mask
Example: 255.255.255.0
5
Gateway IP Address
IP Address
Example: 192.168.1.1
6
RemotEye 4 Installation Date
Date
MM/DD/YYYY
7
Date on RemotEye 4
Date
MM/DD/YYYY
8
Time on RemotEye 4
Times
HH:MM:SS
UPS System
Information
9
UPS Manufacturer
Characters
Toshiba
10
UPS Typeform
Characters
UH3G2L036C61TPA3
11
UPS Serial Number
Characters
2012101234567890
12
UPS Capacity
VA
13
UPS Installation Date
Date
MM/DD/YYYY
14
UPS Firmware Version
Characters
Temp
.
Param
.
15
UPS Battery Temperature
°C
16
UPS Battery Temperature
°F
RemotEye Converts °C to °F = °C * (9/5) + 32
Input Parameters
17
Input Numbers of Phases
Phase
18
Input Voltage
Volts
19
Input Voltage Percent
%
20
Input Current
0.1 Amps
21
Input Current Percent
%
22
Input Rated Current
0.1 Amps
23
Input Frequency
0.1 Hz
24
Input Total Active Power
Watts
25
Input Rated Active Power
Watts
26
Input Apparent Power
VA

Table of Contents