EasyManua.ls Logo

Toshiba RemotEye 4 - Appendix H - - Bacnet Point Mapping for T1000 (1-3 Kva); Bacnet Analog Input Point Mapping for T1000 (1-3 Kva)

Toshiba RemotEye 4
262 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
206 RemotEye 4 User Manual 90988-007
APPENDIX H BACNET POINT MAPPING FOR T1000 (1-3KVA)
H.1 BACNET ANALOG INPUT POINT MAPPING FOR T1000 (1-3KVA)
ALL BACnet Object: Analog Input BACnet Property: Present Value Out of Service: FALSE
Access: Read Only Status Flags: Normal
T1000 (1-3kVA) BACnet Analog Point Mapping
Instance
ID
Object Name & Description
Units
Comments
RemotEye 4 System
Information
1
RemotEye 4 Software Version
Firmware
1.03
2
RemotEye 4 Slave ID Number
ID
3
IP Address
IP Address
192.168.1.150
4
Subnet Mask First Byte
Subnet Mask
55.255.255.0
5
Gateway IP Address First Byte
IP Address
192.168.1.1
6
RemotEye 4 Installation Date
Date
MM/DD/YYYY
7
Date on RemotEye 4
Date
MM/DD/YYYY
8
Time on RemotEye 4
Time
HH:MM:SS
UPS System
Information
9
UPS Manufacturer
Characters
TOSHIBA
10
UPS Typeform
Characters
11
UPS Serial Number
Characters
RX03
12
UPS Capacity
kVA
13
UPS Installation Date
Date
MM/DD/YYYY
14
UPS Firmware Version
Firmware
Temperature
Parameters
15
UPS System Temperature
°C
16
UPS System Temperature
°F
Input
Parameters
17
Input Voltage
Volts
18
Input Voltage Percent
%
19
Input Rated Voltage (V)
Volts
20
Input Frequency
Hz
Output
Parameters
21
Output Voltage
Volts
22
Output Voltage Percent
%
23
Output Rated Voltage
Volts
24
Output Load Percentage
%
25
Output Rated Frequency
Hz

Table of Contents