RemotEye 4 User Manual 90988-007 213
I.2 BACNET BINARY INPUT POINT MAPPING FOR 5000 (3P1)
ALL BACnet Object: Binary Input BACnet Property: Present Value Out of Service: FALSE
Access: Read Only Status Flags: Normal
5000 (3P1) BACnet Binary Point Mapping
Instance ID
Object Name & Description
Units
Comments
RMTI
-4
Status
1
RemotEye 4 Data Link
True/False (1/0)
0 = Link Up; 1 = Link Down
2
RemotEye 4 Network Link
True/False (1/0)
0 = Link Up; 1 = Link Down
UPS Mode
3
Online Mode
True/False (1/0)
4
Backup Mode
True/False (1/0)
5
Bypass Mode
True/False (1/0)
6
Start Inverter
True/False (1/0)
7
Stop Inverter
True/False (1/0)
8
Bypass Inverter On
True/False (1/0)
Battery Status
10
UPS Battery Status Unknown
True/False (1/0)
11
UPS Battery Status Normal
True/False (1/0)
12
UPS Battery Status Low
True/False (1/0)
13
UPS Battery Status Depleted
True/False (1/0)
14
UPS Battery Status Discharging
True/False (1/0)
Battery Charge
Status
16
Protective Charging Set
True/False (1/0)
17
Equalized Charging Set
True/False (1/0)
18
Battery Charger Status Normal Charging
True/False (1/0)
19
Battery Charger Status Stop Charging
True/False (1/0)
20
Battery Charger Status Discharging
True/False (1/0)
EMD
23
EMD Enabled
True/False (1/0)
24
EMD Alarm-1
True/False (1/0)
0 = no Alarm; 1 = Alarm Triggered
(upsAlarmEMDSensor1AlarmTriggered)
25
EMD Alarm-2
True/False (1/0)
0 = no Alarm; 1 = Alarm Triggered
(upsAlarmEMDSensor2AlarmTriggered)
Faults
26
General Alarm Fault
True/False (1/0)
1 = One or more fault reported, see below for cause; 0 = No Faults
Open Fuse Fault
True/False (1/0)
27
EPO has Tripped
True/False (1/0)