RemotEye 4 User Manual – 90988-007 53
Figure 6-8 RemotEye 4 RS-485 Data and GND Cabling
The RS-485 Signal range is:
Input voltage range: 0 to 5 Volts
Output voltage range: -7 to 12 Volts
SOFTWARE CONFIGURATION:
2. On the home page dashboard, click on the SETTINGS hotlink at the top of the page. This will bring up the
SETTINGS drop-down menu . (See Figure 6-9.)
3. In the SETTINGS drop-down menu click on “Interface Settings” the selected entry text will turn RED.
3.1. If using RS-485
3.1.1. Under “RS-485Interface Settings” set RS-485 Interface (Enable/Disable) to “Enabled”, and set
Define RS-485 Interface Protocol to “BACnet”.
3.1.2. Under “RS-232Interface Settings” set RS-232 Interface (Enable/Disable) to “Disabled”, and set
Define RS-232 Interface Protocol to “Disabled”.
3.2. If using RS-232
3.2.1. Under “RS-232Interface Settings” set RS-232 Interface (Enable/Disable) to “Enabled”, and set
Define RS-232 Interface Protocol to “BACnet”.
3.2.2. Under “RS-485Interface Settings” set RS-485 Interface (Enable/Disable) to “Disabled”, and set
Define RS-485 Interface Protocol to “Disabled”.
Figure 6-9 Interface Settings for BACnet MS/TP
4. In the SETTINGS drop-down menu click on “BACnet Settings” the selected entry text will turn RED.
5. Look in the Protocol Settings Panel titled “BACnet Settings”. (See Figure 6-10)
5.1. Under “BACnet MS/TP Settings” set BACnet MS/TP Protocol to “Enabled”,
5.2. Set the Baud Rate to the system baud rate (Default: 9600),
5.3. Set the MS/TP Max Masters (Default: 127),
5.4. Set the Station ID (Default: 1).
6. Under “BACnet IP Settings” set BACnet IP Protocol to “Disabled”.
7. Click on the Set button.